Generator sizing on a mixed-use building is not an adding-up exercise. It is a question of which loads must start together, which ones are motors, and what happens to the voltage when a fire pump and an elevator both try to start a second after the utility drops. Get that right and the generator is often smaller than the first estimate. Get it wrong and the lights dim every time the elevator leaves the lobby.
1. Build the load list by category first
Before any kilowatt number, sort the loads the way the code does: emergency (egress lighting, exit signs, fire alarm), legally required standby (fire pump, smoke control, firefighter elevator) and optional standby (everything the owner wants to keep running). We explained the categories in emergency vs. standby generators for apartment buildings. The generator has to carry the first two categories under all conditions. The third is a business decision, and it is where most of the size comes from.
2. Running load versus starting load
Lighting and electronics draw what their nameplate says. Motors do not. A motor can draw six times its running current for the second or two it takes to come up to speed, and a generator that can carry the running load comfortably may stall or drop voltage badly when a large motor starts. Fire pumps, elevator machines, booster pumps, HVAC compressors and large exhaust fans are all motors. The generator has to be sized for the largest motor-starting event on top of whatever is already running, which is why the sequence of operations matters as much as the total.
3. Fire pumps are the special case
If the building has an electric fire pump on the generator, that pump drives the sizing. The code requires the generator to start the fire pump at locked-rotor current without the voltage sagging more than the fire pump controller allows, and it generally has to do so with the other required loads already connected. A 50 horsepower fire pump can push a generator from the 150 kW range into the 300 kW range on its own. A reduced-voltage or soft-start fire pump controller eases this, but the engineer has to design for it, and the generator manufacturer’s sizing software has to be run with the fire pump’s actual starting characteristics, not a generic estimate.
4. Elevators, and the trick of staggering
Elevators on standby power are usually brought back one car at a time by the elevator controller, which is a form of load staggering built into the equipment. Transfer switches can do the same for other loads: the emergency transfer switch closes first, the legally required loads a few seconds later, the optional loads last. Staggering means the generator never sees all the starting currents at once, and a generator with a modest running capacity can handle a surprisingly large connected load. Regenerative elevator drives add a wrinkle: when a loaded car descends it pushes power back onto the bus, and a generator cannot absorb it. The elevator contractor’s spec should address this, typically with a braking resistor.
5. Mixed-use adds the tenant question
In a mixed-use building the residential side and the commercial side often want different things from the generator. The residential side needs corridors, stairs, elevators and sometimes heat. A restaurant tenant may want its walk-in coolers backed up to protect inventory; a medical or pharmacy tenant may need more. Decide early whether tenant optional loads are on the house generator at all. If they are, each tenant feed needs its own metering and transfer arrangement so the landlord can recover the cost, and the generator grows accordingly. If they are not, say so in the lease and let the tenant provide its own.
6. The numbers to hand the engineer
The generator manufacturer’s sizing tool needs: every load by category with its running kW, every motor with horsepower and starting method, the order in which the transfer switches close, the allowable voltage dip, the fuel type and the required run time. With those, the engineer lands on a size with margin for growth, and the contractor can price the generator, the transfer switches, the fuel and the pad or roof structure accurately. Without them, every bidder guesses, and the guesses do not match.